UP36 Set Up Guide

UP36 with Front Cover
up36opt

UP36 with Front Cover Removed

UP36TopOff

First you must set the Dip Switches to
ADVANCED & SUPPLY

UP36SDip1Up

Next you Press the Item, Up & Down
Buttons Together for 2 seconds +
UP36SetButs

 ROOM occ appears on the screen display

Using the Up or Down Buttons the room temperature can then be selected i.e. 21c

After the Room occ temperature is selected

Press the Item Button
to move to the next Item Field

i.e. Room unocc

The Item Button

must be Pressed after each Field settings
have been selected

The following is a list of the Default Settings for the UP36

UP36ItemF_1to11

UP36ItemF12to13

On completion of the above settings
press the Item Button till ESC appears

You then press either the UP or DOWN button
to come out of the set up mode

Once out of the Set Up Mode
Reset the the dip switch to the 
Down Position
UP36SDipsDown

Oil Boilers

Note:- with oil boilers, `BOILER Min`
Requires a setting to 45c,
With the sensor positioned on the pipework return.

Also move the MIDDLE & RIGHTHAND Dipswitches
to the top postion respectively